MEAN WELL DIN Rail Series: HDR, MDR, EDR, NDR and SDR
HDR-60, MDR-60, EDR-120, NDR-120 and SDR-240 in one 24V table: size, overload mode, peak load, DC OK, efficiency, temperature and EMC class.
Use the DIN-rail family code only to open the right set of PDFs, then compare exact models at the same output voltage. In a 24V reference set, HDR-60 and MDR-60 share a 60W rating but differ in width, depth, overload behaviour and DC OK signalling; EDR-120 and NDR-120 share a 120W rating and the same body but differ in working temperature and emission class; SDR-240 adds PFC, a documented short-term peak and a DC OK contact at 240W. A family name never substitutes for another family's documented behaviour, so the final choice is always an exact model checked against your load, cabinet and signal requirements.
What HDR, MDR, EDR, NDR and SDR Codes Mean
A MEAN WELL DIN-rail family code such as HDR, MDR, EDR, NDR or SDR identifies a product series, not a set of properties you can assume. Neither the code nor the wattage in the model number tells you the output adjustment range, how the unit behaves in overload, its width and depth, whether it offers a DC OK contact, its emission class or its working temperature range. Those come from the exact model's PDF.
Two pairs from the reference set show why. EDR-120 and NDR-120 share the same 40*125.2*113.5mm body and the same 24V, 5A rating, yet EDR-120 lists a working temperature of -20 ~ +60℃ and Class A emission while NDR-120 lists -20 ~ +70℃ and Class B. HDR-60 and MDR-60 share a 60W rating but differ in width, depth, overload behaviour and signals.
24V Reference Set: HDR-60, MDR-60, EDR-120, NDR-120, SDR-240
Compare like with like: the same output voltage and, where possible, the same power. This guide uses 24V models: HDR-60-24 and MDR-60-24 at 60W, EDR-120-24 and NDR-120-24 at 120W, and SDR-240-24 at 240W. All values come from their current PDFs, and the family pages hold the other voltages and power levels.
Within each pair the output rating is identical, so every difference in the matrix is a design difference rather than a size-class difference. SDR-240-24 stands alone at its power level and is included to show what a higher-power DIN-rail family adds.
MEAN WELL DIN Rail Feature Matrix
The matrix uses only the readable rows of each PDF. 'Not listed' means the cited pages give no such row, not that the feature is confirmed absent.
| Check | HDR-60-24 | MDR-60-24 | EDR-120-24 | NDR-120-24 | SDR-240-24 |
|---|---|---|---|---|---|
| Rated output | 24V, 2.5A, 60W | 24V, 2.5A, 60W | 24V, 5A, 120W | 24V, 5A, 120W | 24V, 10A, 240W |
| Output adjustment | 21.6 ~ 29V | 24 ~ 30V | 24 ~ 28V | 24 ~ 28V | 24~28V |
| Size (W*H*D) | 52.5*90*54.5mm | 40*90*100mm | 40*125.2*113.5mm | 40*125.2*113.5mm | 63*125.2*113.5mm |
| AC input | 85 ~ 264VAC (277VAC operational) | 85 ~ 264VAC | 90 ~ 264VAC | 90 ~ 264VAC | 88 ~ 264VAC, PFC |
| Overload behaviour | 105 ~ 160%; hiccup below 50% output voltage | 105 ~ 150%, constant current | 105 ~ 130%, constant current | 105 ~ 130%, constant current | 110 ~ 150% for over 3 seconds, then shutdown |
| Peak capability | Not listed | Not listed | Not listed | Not listed | 15A, 360W for 3 seconds |
| DC OK contact | Not listed | Relay contact | Not listed | Not listed | Relay contact |
| Typical efficiency | 90% | 87% | 87.5% | 88% | 94% |
| Working temperature | -30 ~ +70℃ | -20 ~ +70℃ | -20 ~ +60℃ | -20 ~ +70℃ | -25 ~ +70℃ |
| EMC emission class | Class B | Class B | Class A | Class B | Class B |
DIN Rail Width, Depth and Feature Trade-offs
When panel width is the constraint, compare width and depth together. MDR-60, EDR-120 and NDR-120 are 40mm wide, HDR-60 is 52.5mm wide but only 54.5mm deep, and SDR-240 is 63mm wide. Per millimetre of rail that is about 1.5W/mm for MDR-60-24, 1.1W/mm for HDR-60-24, 3.0W/mm for EDR-120-24 and NDR-120-24 and 3.8W/mm for SDR-240-24, but the spacing each PDF recommends still has to be added, such as 5mm left and right for EDR-120 and NDR-120 when loaded permanently with full power.
When features lead, start from the requirement. A DC OK relay contact appears in the readable rows of MDR-60 and SDR-240, a short-term peak rating only for SDR-240, the widest working-temperature range for HDR-60, and Class A emission only for EDR-120. HDR-60 also lists isolation class II and Pass LPS in a plastic housing. Each of these narrows the family before an exact model is chosen.
From DIN Rail Series to Exact Model
Once the family is narrowed, move to the exact model: output voltage and adjustment range, rated current with derating at your cabinet temperature, input range, protection behaviour and any signal contacts. Then check the terminal drawing and mounting notes for that model before ordering. The DIN-rail collection and the family pages list the available voltages and power levels.
For a PLC or control-cabinet project, the application page adds the load and backup questions that a family comparison does not answer.
Common Pairwise Questions: HDR, MDR, EDR, NDR, SDR
The same pairings come up repeatedly. The answers below restate the documented differences; none of them makes one family a substitute for another.
- HDR versus MDR: at 24V and 60W, HDR-60 is 52.5mm wide and 54.5mm deep with isolation class II and an overload band of 105 ~ 160%; MDR-60 is 40mm wide and 100mm deep with constant current limiting at 105 ~ 150% and a DC OK relay contact
- EDR versus NDR: the same 40*125.2*113.5mm body and 24V, 5A rating; NDR-120 lists -20 ~ +70℃ and Class B emission, EDR-120 lists -20 ~ +60℃ and Class A emission
- NDR versus SDR: SDR-240 adds PFC, a 360W peak for 3 seconds, a DC OK relay contact and 94% typical efficiency at 24V, in a 63mm-wide body
- HDR versus NDR: HDR-60 accepts 85 ~ 264VAC with 277VAC operational, while NDR-120 accepts 90 ~ 264VAC
Frequently asked questions
Can I replace one DIN rail family with another?
Not by family name alone. Treat it as a new selection: match the output voltage and adjustment range, current and derating, input range, overload behaviour, signals, emission class, dimensions and terminal layout from the exact PDFs. Even EDR-120-24 and NDR-120-24, with identical ratings and bodies, differ in working temperature and emission class.
What changes besides the wattage?
Width and depth, input range, overload mode, peak capability, DC OK signalling, efficiency, working temperature and emission class all vary across the reference set. At 60W alone, HDR-60 and MDR-60 differ in most of those, from a 52.5mm against a 40mm width to hiccup-then-constant-current against constant current overload behaviour.
Where should I start when panel width is limited?
Start from the width and depth each PDF lists and add its recommended clearances. In the reference set the 40mm-wide 120W units deliver the most output per millimetre of rail after SDR-240, and HDR-60 is the shallowest at 54.5mm deep; confirm derating at your cabinet temperature before choosing.
Information needed for a configuration check
- Output voltage and continuous and peak current of the load
- Available rail width and cabinet depth
- Cabinet internal temperature and airflow
- Required signals such as DC OK, and the EMC class the equipment needs
- Site mains voltage range
Manufacturer documents used
- HDR-60-SPEC.PDF, consulted pages 1, 2
- MDR-60-SPEC.PDF, consulted pages 1, 2
- EDR-120-SPEC.PDF, consulted pages 1, 2
- NDR-120-SPEC.PDF, consulted pages 1, 2
- SDR-240-SPEC.PDF, consulted page 1