Power supply inrush current

Power Supply Inrush Current: What Buyers Should Check

Inrush vs steady-state input current, cold-start test conditions, units per breaker, and typical inrush for LRS-350, NDR-240, UHP-350, LPV-100 and PCD-60.

Power Supply Inrush Current: What Buyers Should Check

Inrush current is the brief surge a power supply draws when it is switched on, and it is far larger than the running input current: LPV-100, for example, lists 75A of cold-start inrush against an AC current of 1.2A at 230VAC. Read each inrush figure with its printed conditions, check any documented limit on units per breaker, and bring the quantity, input circuit and switching pattern to a qualified designer. This guide explains the specifications; it does not size breakers or prescribe wiring.

Inrush Current vs Steady-State Input Current

Inrush current is the short surge a supply draws from the mains at switch-on, largely while its input stage charges. Steady-state input current is what it draws afterwards while running. A PDF lists the two in separate rows, and they should never be read as the same thing.

The difference is large. At 230VAC, LPV-100 lists an AC current of 1.2A and a cold-start inrush current of 75A, about 62 times higher; NDR-240 lists 1.3A against 35A, about 27 times; LRS-350 lists 3.4A against 60A, about 18 times. The steady figure describes the running load on a circuit, while the inrush figure concerns the first instant after switch-on.

Inrush Current Test Conditions: Cold Start and Input Voltage

An inrush figure means little without its conditions. Check whether it is typical or maximum, whether it is a cold start, at which input voltage it was measured, and whether a pulse width is given. The five PDFs used here state their inrush rows differently, as the table shows.

Tolerances matter too. UHP-350 adds in Note 8 that its inrush parameter has 10% tolerance, so its 60A/230VAC figure covers roughly 54A to 66A. None of these pages states the source impedance behind the measurement or the behaviour on a quick restart, so both remain questions for the supplier.

Inrush rows and their printed conditions
Series Inrush (typical) Conditions printed AC current (typical)
LPV-100 75A at 230VAC Cold start; twidth=700μs measured at 50% Ipeak 2.2A/115VAC, 1.2A/230VAC
PCD-60 13A at 230VAC Cold start; twidth=50μs measured at 50% Ipeak 0.6A/230VAC, 0.5A/277VAC
LRS-350 60A/115VAC, 60A/230VAC Typical value 6.8A/115VAC, 3.4A/230VAC
NDR-240 20A/115VAC, 35A/230VAC Typical value 2.5A/115VAC, 1.3A/230VAC
UHP-350 30A/115VAC, 60A/230VAC Cold start; 10% tolerance per Note 8 4A/115VAC, 2A/230VAC

Several Power Supplies Starting on One Breaker

When several supplies share a circuit and are switched on together, their inrush currents can overlap. Some PDFs document how many units one breaker can take: LPV-100 lists a maximum of 2 units on a 16A type B breaker or 3 on type C at 230VAC, while PCD-60 lists 32 units on either type.

Hypothetically, six LPV-100 units on one 16A type B circuit, switched on together, would exceed the documented count of 2. Adding their typical peaks, 6 × 75A = 450A, only illustrates an upper bound, because peaks need not coincide and each is a pulse about 700μs wide at 50% Ipeak. The documented count, not the summed peak, is the figure to bring to the circuit designer, who decides how the units are divided.

Units per Breaker and Other Documented Limits

Use only the mitigation the documents support. On the cited pages the documented tool is the per-breaker unit count for the stated breaker type and input voltage; none of the pages lists an inrush-limiting accessory or a soft-start option.

Other approaches, such as switching groups of supplies in sequence, splitting them across circuits or changing breaker characteristics, are circuit-design decisions for a qualified designer. This guide does not prescribe breaker ratings, breaker types or wiring changes.

Inrush Current Questions for Your Supplier

Bring these points to the quotation so that the answer rests on the exact documents rather than on an isolated peak value.

  • Exact part numbers and the quantity on each circuit
  • Site input voltage and frequency, and the breaker type and rating already installed
  • Whether all units switch on together, in groups or one at a time
  • Restart pattern: cold starts only, or frequent on-off cycling
  • Other loads on the same circuit and their own inrush
  • Whether a typical or maximum inrush value is needed, with its pulse width

Inrush Current in Power Supply Sizing

Inrush is one input-side check within overall sizing; the sizing guide covers the load budget, startup demand and derating. For enclosed and DIN-rail candidates, compare the input rows of each exact PDF, including AC current, inrush conditions and any breaker-count row, before shortlisting.

Frequently asked questions

Is inrush the same as rated input current?

No. The typical AC input current describes the running condition, while inrush is the brief surge at switch-on. For NDR-240 at 230VAC, the PDF lists 1.3A of AC current and 35A of inrush.

Does a larger breaker always solve the problem?

No. The breaker protects the circuit and its wiring, and a qualified designer chooses its rating and type. Where a PDF gives a unit count per breaker, such as 2 LPV-100 units on a 16A type B breaker at 230VAC, that count is the documented limit to design around.

Can I use only the peak value to assess compatibility?

No. A peak needs its conditions, meaning typical or maximum, cold start, input voltage, pulse width and tolerance, plus the number of units, how they switch on, the rest of the circuit and the breaker's own characteristics. A peak without that context can neither confirm nor rule out a circuit arrangement.

Information needed for a configuration check

  • Exact part numbers and quantity per circuit
  • Site input voltage and frequency, and the installed breaker type and rating
  • Switching pattern: together, in groups or one at a time
  • Restart pattern and other loads on the same circuit

Manufacturer documents used