Power supply voltage drop

Power Supply Voltage Drop Under Load: Checks and Causes

Why output voltage sags under load: terminal vs load voltage, cable and connector drop, overload behavior of LRS-350, NDR-240 and HDR-60, and a checklist.

Power Supply Voltage Drop Under Load: Checks and Causes

Voltage drop under load usually comes from one of three places: losses in the cables and connectors between supply and load, a load that exceeds the supply's rated or derated output so that its overload behaviour takes over, or the regulation limits printed for the model, such as the ±1.0% tolerance of the 24V examples here. Measure at both the supply and the load terminals, compare the load current with the exact model's ratings, and read its overload mode before changing anything. Turning up the output adjustment is not a default fix, and a symptom alone is not a diagnosis.

Voltage at the Terminals vs at the Load

First establish where the low voltage is seen. The supply regulates its own output terminals; the load sees that voltage minus whatever is lost in cables, connectors and protective devices on the way. A reading at the load that is lower than the reading at the supply terminals points to the wiring, while a low reading at the supply terminals themselves points to the supply's operating point.

Record how and when each reading was taken: with or without the load running, at which terminals and with which instrument. Measurements on live installations should be made by qualified personnel following the site's safety rules; this guide does not describe live probing.

Load Current vs Rated Output: LRS-350, NDR-240, HDR-60

Next compare the actual load with what the exact model documents. LRS-350-24 is rated at 14.6A, NDR-240-24 at 10A and HDR-60-24 at 2.5A, all at 24V. Each specification also defines how far the output may move: all three 24V columns list ±1.0% voltage tolerance, which includes setup tolerance, line regulation and load regulation, so the terminal voltage may lie between 23.76V and 24.24V at the stated test conditions.

Load regulation shows how much of that comes from load changes: ±0.5% for LRS-350, measured from 0% to 100% rated load, and ±1.0% for NDR-240 and HDR-60. Record the continuous and startup current of the load and check derating at the actual ambient temperature, because a load inside the nameplate rating can still exceed the derated output.

Cable and Connector Voltage Drop

Cable and connector resistance turns current into voltage drop. A labelled example with hypothetical values: an 8A load fed through a cable pair whose total loop resistance, out and back, is 0.05Ω loses 8A × 0.05Ω = 0.4V, so a supply set to 24.0V delivers about 23.6V at the load. That 1.7% drop is larger than the ±1.0% tolerance of the supply itself.

Terminal screws, connectors, fuses and long runs all add resistance, and resistance rises with temperature and with loose connections. The cable size for an installation comes from the equipment maker and the installer's rules; the example only shows why the location of the measurement matters.

Overload Behavior and Output Regulation by Series

If the load asks for more than the supply can deliver, the overload behaviour decides what the voltage does, and it differs by series. NDR-240 lists constant current limiting at 105 ~ 130% rated output power with automatic recovery, so an overloaded unit holds its current and the output voltage falls. HDR-60 lists constant current limiting while the output stays within 50% ~100% of rated voltage and hiccup mode below 50%, across 105 ~ 160% rated output power. LRS-350 lists hiccup mode at 110 ~ 140% for its 3.3~36V models, so the output cycles rather than settling at a lower voltage.

A steady low voltage under heavy load is therefore consistent with current limiting on NDR-240 or HDR-60, while a cycling output is consistent with hiccup. Both are possible explanations to check against the measured current; the protection guide explains the modes in detail.

Recent Changes and Temperature Effects

Voltage drop often follows a change. Collect what changed before the symptom appeared; temperature effects are covered in more depth in the derating and overheating guides.

  • Loads added to the output since the last correct reading
  • Wiring changes: longer runs, new connectors, extra fuses or terminals
  • Changes to the output voltage adjustment
  • Lower mains voltage at the site; NDR-240 Note 4 warns that derating may be needed under low input voltage
  • Higher cabinet temperature or blocked airflow, which reduce the derated output

Voltage Drop Support Checklist

A complete record lets support separate a supply issue from a wiring or load issue without guessing. Collect the items below before requesting help.

  • Exact model number and suffix, and the document revision used
  • Output voltage at the supply terminals and at the load, with and without load, and how it was measured
  • Continuous and startup load current, measured by qualified personnel
  • Cable length and type, connectors and protective devices between supply and load
  • Input voltage, ambient temperature and mounting
  • Whether the output is steady, sagging or cycling, and any adjustment already made

Frequently asked questions

Does low voltage mean the supply is faulty?

Not necessarily. Cable and connector losses, a load above the rated or derated output, current limiting, low mains and a changed adjustment can all lower the voltage the load sees. Compare the reading at the supply terminals with the ±1.0% tolerance of the 24V column before suspecting the supply itself.

Can cable length matter?

Yes. Voltage drop equals current times loop resistance, and resistance grows with length. In the hypothetical example, 8A through 0.05Ω loses 0.4V, more than the supply's own ±1.0% tolerance at 24V.

Should I just turn up the voltage adjustment?

Not as a default. The adjustment range is limited and sits close to the OVP range: LRS-350-24 adjusts up to 28.8V, the lower end of its 28.8 ~ 33.6V OVP range, and NDR-240-24 adjusts up to 28V against 29 ~ 33V. Raising the set-point can also hide an overload or wiring fault, so find the cause first and only then consider an adjustment inside the printed range.

Information needed for a configuration check

  • Exact model number, suffix and document revision
  • Voltage at the supply and load terminals, with and without load, and the measurement method
  • Continuous and startup load current
  • Cable length and type, connectors and protective devices in the output circuit
  • Input voltage, ambient temperature and mounting