Industrial Power Supply Efficiency: Compare Like for Like
Turn efficiency into watts and kWh: annual loss for LRS-350-24, RSP-320-24 and UHP-350-24 at 250W, plus power factor, cooling, size and no-load power.
Compare industrial power supply efficiency only at matching stated conditions, and read it as the ratio of DC output to AC input, not as a cut in rated output. The three 24V examples here list typical efficiencies of 88% for LRS-350-24, 89% for RSP-320-24 and 94% for UHP-350-24, each at rated load and, where the PDF states it, 230VAC input. Turn the percentages into watts of loss and heat for your own load, confirm partial-load efficiency with the supplier, and weigh the result alongside derating, power factor and cooling.
Efficiency, Input Power and Power Loss
Efficiency is the DC output power divided by the AC input power at a stated operating point; the difference between the two is loss, dissipated as heat. The rated power in a PDF is the DC output: LRS-350-24 is rated at 350.4W, RSP-320-24 at 321.6W and UHP-350-24 at 350.4W, all at 24V.
At rated load, the typical efficiencies of 88% for LRS-350-24, 89% for RSP-320-24 and 94% for UHP-350-24 imply input powers of about 398.2W, 361.3W and 372.8W, and losses of about 47.8W, 39.7W and 22.4W. Efficiency is never subtracted from the nameplate: each unit still delivers its full rated DC output, and efficiency only says how much extra input it draws to do so.
Efficiency Measurement Conditions
A percentage without its conditions cannot be compared. LRS-350 and UHP-350 both state in Note 1 that parameters not specially mentioned are measured at 230VAC input, rated load and 25℃ ambient, so their efficiency rows are full-load figures at that input. UHP-350 adds in Note 7 that its figures apply only to the Blank type and that the R type, with DC OK and redundancy, is slightly less efficient.
Check the wording too. The rows are marked typical, not minimum, and headline figures differ from column figures: the LRS-350 description quotes efficiency up to 89% for the series while its 24V column lists 88%, and UHP-350 quotes up to 94%, which is also its 24V figure. The RSP-320 page used here gives the typical row and its power-factor conditions, but its notes are not readable in this copy, so confirm its measurement conditions with the supplier.
Efficiency vs Load and Input Voltage Curves
A single typical value at rated load says nothing about how efficiency changes at lighter loads or lower input voltages, and most loads do not run at full rating all the time. None of the three pages used here includes an efficiency-versus-load curve, so no partial-load figure can be read from them.
Where a PDF provides a curve, compare candidates at the same input voltage and the same load point. Where it does not, ask the supplier for efficiency at your expected load and site voltage rather than estimating it; the calculation below states its assumption explicitly for that reason.
Annual Energy Loss: LRS-350-24, RSP-320-24, UHP-350-24
Hypothetical example: a 250W continuous load, 8760 hours of operation per year and a tariff of 0.15 currency units per kWh. For illustration only, the calculation assumes that each unit's rated-load typical efficiency also applies at 250W; the real partial-load efficiency may differ.
The result is a planning estimate, not a promised saving. Replace the assumed efficiency with measured or supplier-confirmed values at your load, and use your own operating hours and tariff.
| Model | Typical efficiency at rated load | Input at 250W | Loss | Annual loss energy | Annual loss cost |
|---|---|---|---|---|---|
| LRS-350-24 | 88% | 284.1W | 34.1W | 298.6 kWh | 44.8 |
| RSP-320-24 | 89% | 280.9W | 30.9W | 270.7 kWh | 40.6 |
| UHP-350-24 | 94% | 266.0W | 16.0W | 139.8 kWh | 21.0 |
Power Loss as Heat in the Enclosure
Every watt of loss becomes heat inside the enclosure. In the example the loss ranges from about 16.0W to 34.1W, and at rated load from about 22.4W to 47.8W; the cabinet's ventilation has to remove that heat along with the heat from other equipment.
Efficiency and derating are separate checks. A more efficient unit adds less heat, but its usable output at a given ambient still comes from its own derating curve and mounting conditions: LRS-350 uses forced air cooling by a built-in DC fan, while UHP-350 is a fanless design. The derating guide covers those curves, and the sizing guide covers the load budget.
Efficiency Alongside Power Factor, Cooling and Size
Use efficiency as one line in a wider comparison. The same three records also differ in input power factor, cooling, size and features, as the matrix shows.
Approvals and load dynamics belong in the same comparison: check each PDF's safety standards and its overload and peak behaviour for your application before choosing.
| Check | LRS-350-24 | RSP-320-24 | UHP-350-24 |
|---|---|---|---|
| Rated output | 24V, 14.6A, 350.4W | 24V, 13.4A, 321.6W | 24V, 14.6A, 350.4W |
| Typical efficiency | 88% | 89% | 94% (Blank type) |
| Power factor | No PF row listed | PF>0.95/230VAC | PF≥0.94/230VAC |
| Cooling | Built-in DC fan | Not stated on the cited page | Fanless |
| Size | 215*115*30mm | 215*115*30mm | 220*62*31mm |
| No-load power | <0.75W | Not stated on the cited page | Not stated on the cited page |
| Signals | Not listed | Not stated on the cited page | DC OK and redundancy optional (R type) |
Frequently asked questions
Does 90% efficiency mean only 90% of rated output is usable?
No. The rated power is the DC output the unit can deliver, and efficiency describes the input needed to deliver it. LRS-350-24 still delivers its 350.4W rating at 88% typical efficiency; it simply draws about 398.2W from the mains at rated load.
Can I compare two peak figures directly?
Only when both were measured under the same conditions: input voltage, load point, temperature and product variant. A series headline such as up to 89% for LRS-350 is not its 24V column value of 88%, and the UHP-350 figures apply to its Blank type only.
Is the PC PSU efficiency label the right criterion here?
No. PC power-supply efficiency labels test PC units at their own load points, while industrial supplies are specified by the conditions in their own PDFs. Compare typical values at matching stated conditions, ask for data at your operating point, and weigh efficiency alongside derating, power factor, cooling and approvals.
Information needed for a configuration check
- Expected load profile and operating hours
- Site input voltage
- Efficiency data at the expected load point, from the supplier
- Cabinet ventilation capacity and ambient temperature
- Local electricity tariff
Manufacturer documents used
- LRS-350-SPEC.PDF, consulted pages 1, 2
- RSP-320-SPEC.PDF, consulted page 3
- UHP-350-spec.pdf, consulted pages 1, 2