SDR and NDR are both MEAN WELL single-output DIN rail power supplies with the same widths at each power rating. The practical differences are what happens above rated load and what the unit reports: SDR is specified for a 150% peak for 3 seconds and has a DC OK relay contact, while NDR limits current at 105 ~ 130% of rated power and its datasheets list no relay contact. SDR is also the more efficient of the two at 120W and above, and adds a 960W size.

SDR vs NDR at 24V: Specification Table

24V models, values as printed in each datasheet
Item SDR-120-24 NDR-120-24 SDR-240-24 NDR-240-24 SDR-480-24 NDR-480-24
Rated current / power 5A / 120W 5A / 120W 10A / 240W 10A / 240W 20A / 480W 20A / 480W
Peak (3 s) 7.5A / 180W not listed 15A / 360W not listed 30A / 720W not listed
Overload >150%, constant current; shuts down after 3 s 105 ~ 130%, constant current, auto-recovery >150%, constant current; may shut down after 2 s 105 ~ 130%, constant current, auto-recovery >150%, constant current; may shut down after 2 s 105 ~ 130%, constant current; shuts down after 3 s
AC input 88 ~ 264VAC 90 ~ 264VAC 88 ~ 264VAC 90 ~ 264VAC 90 ~ 264VAC 90 ~ 264VAC
Efficiency (typ.) 91% 88% 94% 88.5% 94% 92.5%
Ripple & noise (max.) 100mVp-p 120mVp-p 50mVp-p 150mVp-p 100mVp-p 150mVp-p
Hold-up (230VAC, full load) 20ms 16ms 20ms 28ms 14ms 16ms
DC OK relay contact Yes not listed Yes not listed Yes not listed
Working temperature -25 ~ +70℃ -20 ~ +70℃ -25 ~ +70℃ -20 ~ +70℃ -25 ~ +70℃ -20 ~ +70℃
Size (W × H × D) 40 × 125.2 × 113.5 mm 40 × 125.2 × 113.5 mm 63 × 125.2 × 113.5 mm 63 × 125.2 × 113.5 mm 85.5 × 125.2 × 128.5 mm 85.5 × 125.2 × 128.5 mm

At 75W the two are closest: SDR-75-24 and NDR-75-24 share the 32 × 125.2 × 102 mm case and the 3.2A rating, with typical efficiency of 89% and 88%. SDR-960-24 (40A, 960W, 110 mm wide) has no NDR equivalent and needs 180 ~ 264VAC input.

Peak Load and Overload Behaviour

This is the difference that decides most selections. The SDR datasheets give a peak current and peak power for 3 seconds, 150% of rating, and describe overload above 150% as constant current limiting. A load that draws a short inrush, such as a solenoid, a contactor coil or a small motor starting, can be carried by SDR within that window. The NDR datasheets give no peak rating; overload protection starts at 105 ~ 130% of rated power with constant current limiting. On NDR, a start-up surge beyond that band will pull the output voltage down rather than being delivered.

Recovery differs too. NDR-120 and NDR-240 recover automatically once the fault is removed; NDR-480 shuts down after 3 seconds and needs re-powering. SDR-120 shuts the output down after 3 seconds of overload, and SDR-240 and SDR-480 may shut down after 2 seconds.

Monitoring: DC OK Relay

SDR-120, SDR-240 and SDR-480 have a DC OK relay contact: closed when the supply is on and the output is good, open on DC fail, rated 30V/1A resistive. It can be wired to a PLC input to report a supply failure. The NDR-120, NDR-240 and NDR-480 datasheets do not list a relay contact, so a status signal there has to come from elsewhere.

Efficiency, Ripple and Power Factor

From 120W upwards SDR is more efficient at 24V: 91% against 88% at 120W, 94% against 88.5% at 240W and 94% against 92.5% at 480W. At 240W that is roughly 15W against 31W of heat inside the cabinet at full load (calculated from the typical efficiencies). SDR-240-24 also lists lower ripple, 50mVp-p against 150mVp-p. Both SDR-120 and up and NDR-240 and up have PFC; the NDR-75 and NDR-120 datasheets do not list a power factor.

Where NDR Is the Better Fit

For a steady load well inside the rating, NDR does the job at the same width. NDR-240-24 has the longer hold-up of the 240W pair, 28ms against 20ms at 230VAC full load, which helps ride through a short mains dip. Approvals also differ by model: NDR-240 lists BIS IS13252 and BSMI CNS14336-1 among its approvals, so check the exact datasheet against the approvals your market requires.

Is SDR a Drop-In Replacement for NDR?

Mechanically, at the same rating the listed width, height and depth are identical, so an SDR fits the rail space an NDR occupies. Electrically, SDR adds DC OK terminals, accepts a slightly lower input (88VAC on the 75W to 240W models) and behaves differently in overload. Confirm the terminal assignment, the overload and recovery behaviour your system expects and the approvals on the exact datasheet before swapping one for the other.

Frequently asked questions

Which is better for motors and solenoids?

SDR, where the start-up surge stays within its 150% peak for 3 seconds. NDR lists no peak rating and limits current from 105 ~ 130% of rated power.

Do SDR and NDR take the same rail space?

Yes, at the same power rating the listed dimensions are identical, from 32 mm wide at 75W to 85.5 mm at 480W.

Does NDR have a DC OK output?

The NDR-120, NDR-240 and NDR-480 datasheets list no DC OK relay contact. SDR-120, SDR-240 and SDR-480 have one, rated 30V/1A.