LED strip power supplies

How to Size a Power Supply for LED Strip Lights

Work out LED strip load in watts, allow for cable voltage drop and derating, and compare LPV-100-12 vs LPV-100-24 in a worked example.

How to Size a Power Supply for LED Strip Lights

To size a supply for constant-voltage LED strip, match the strip's labelled voltage first. Then multiply its documented consumption per metre by the installed length of every run that is lit at the same time, add the controller's own consumption, and convert the total to current at the strip voltage. Compare that current with a candidate's rating after reading its derating curve for the installation ambient, and treat cable voltage drop, feed arrangement and dimming limits as separate checks set by the strip and controller manufacturers. The worked example is hypothetical and uses LPV-100-12 and LPV-100-24 only as constant-voltage candidates; the LPV-100 datasheet states the series is not intended for LED lighting luminaire applications in the EU and China.

LED Strip Label and Installation Data

Sizing starts with the strip's own documents, not with a generic figure per metre. Before choosing a supply, collect the strip label or datasheet and its installation instructions, and record what they state rather than what similar strips usually draw. Consumption varies widely between strip products, so a value copied from another strip is only a guess.

Constant-voltage strips, the kind sized in this guide, are labelled with a nominal input voltage such as 12V or 24V and a consumption in watts or amperes per metre. Constant-current LED modules follow a different method and need a constant-current driver instead.

  • Nominal input voltage, and confirmation that the strip is a constant-voltage type
  • Documented consumption in W/m or A/m, and the condition it is stated at
  • Planned length of each run and how the runs are grouped
  • Maximum run length per feed and the feed arrangement, from the strip manufacturer
  • Controller or dimmer model, its channel current limits and its own consumption
  • Installation environment: indoor or outdoor, enclosure, ambient temperature, water and sunlight exposure

Calculating LED Strip Load in Watts

The connected load is the documented consumption multiplied by the installed length for every run that can be lit at the same time, plus anything else on the same DC output, such as a controller. Convert the total to current at the strip voltage, because the supply's current rating at that voltage is the limit that matters.

Every value in the worksheet is hypothetical and only shows the units. Replace it with your strip's documented consumption and your measured run lengths, and keep the condition under which the consumption is stated.

Load worksheet with units (hypothetical example values)
Item Length or count Documented value Result Source
Strip run A 2.5m 14.4W/m 36W Strip datasheet (reader input)
Strip run B 2.5m 14.4W/m 36W Strip datasheet (reader input)
Strip run C 1.5m 14.4W/m 21.6W Strip datasheet (reader input)
Strip total 6.5m - 93.6W Calculated
PWM controller, own consumption 1 0.1A 0.1A Controller datasheet (reader input)
Total current, 24V version - 93.6W / 24V = 3.9A 4.0A Calculated
Total current, 12V version - 93.6W / 12V = 7.8A 7.9A Calculated

Cable Voltage Drop and LED Strip Installation Losses

The calculated load is what the strips draw at their rated voltage; it says nothing about how that voltage arrives. Every cable between supply and strip, and the strip's own copper, drops voltage in proportion to current, so the far end of a long run receives less than the supply output and can look dimmer or shift colour.

The strip voltage changes the size of this effect. For the same 93.6W, the 12V version draws 7.8A against 3.9A at 24V; through the same cable resistance the drop doubles, and as a share of the bus voltage it becomes four times larger. That is why the strip manufacturer's maximum run length per feed and feed arrangement decide how the runs are wired. This guide does not prescribe feed points, cable sizes or run lengths.

The LPV-100 specification lists no output voltage adjustment range, so with this candidate a drop cannot be offset by trimming the output; it has to be handled in the layout that the strip manufacturer and the installer specify.

LED Strip Dimming and Controller Placement

First establish where dimming happens. Some sources dim their own output; a constant-voltage supply without a dimming function stays at its fixed voltage, and a controller between supply and strip does the dimming. The LPV-100 specification describes a constant voltage design and lists no dimming function, so in the example the PWM controller does the dimming.

That adds two limits to the chain. The controller's channel and total current ratings must cover the runs connected to it, and its own consumption belongs in the load budget, as the 0.1A row in the worksheet shows. Check the controller's input voltage range as well; without its datasheet, those values stay open inputs rather than assumptions.

LPV-100 Temperature Derating for LED Strip Supplies

The LPV-100 working temperature is listed as -25 ~ +70℃ with a reference to the derating curve. The page 2 curve, drawn for HORIZONTAL mounting, has separate lines labelled 5V,12V and Others, so LPV-100-12 follows a different derating line from LPV-100-24 at the same ambient. Read the correct line for the actual installation temperature, as the derating guide explains, instead of applying one line to both models.

Note 4 adds that derating may be needed under low input voltage and points to the static characteristics, and Note 8 requires ambient derating of 3.5℃/1000m for fanless models operating above 2000m.

For water and sun, the specification lists a fully encapsulated IP67 level, Note 7 limits outdoor use to locations without direct sunlight exposure, and Note 10 refers water-proof installation cautions to the MEAN WELL user manual. That rating belongs to the supply alone: connections, strip, controller and enclosure each need their own rating, and one IP67 component does not make the installation IP67.

If the lighting is a luminaire application in the European Union or China, LPV-100 Note 11 states that the product is not intended for that use and names other MEAN WELL series instead; the feature list positions LPV-100 for LED decoration or advertisement devices.

LPV-100-12 vs LPV-100-24 for an LED Strip Load

The matrix compares only what the LPV-100 PDF and product records document against the hypothetical load. It records headroom and open checks; it does not approve either model for a real installation. For a wider choice of models, use the strip-light supply page.

Both options use more than 90% of rated current before any derating is applied, so neither can be accepted until the curve line for the installation ambient has been read. If the usable current is below the load, the usual paths are to split the runs across two supplies or to choose a higher rating, with the feed arrangement confirmed by the strip manufacturer.

Candidate comparison for the hypothetical strip installation
Check LPV-100-12 LPV-100-24
Rated output 12V, 8.5A, 102W 24V, 4.2A, 100.8W
Typical efficiency 85% 88%
Hypothetical load current 7.9A 4.0A
Share of rated current About 93% About 95%
Derating line on page 2 5V,12V Others
Input and overload (series rows) 90 ~ 264VAC; 110 ~ 150% hiccup 90 ~ 264VAC; 110 ~ 150% hiccup
Enclosure and use notes IP67; outdoor only without direct sunlight; EU and China luminaire restriction IP67; outdoor only without direct sunlight; EU and China luminaire restriction
Recorded decision Hold: read the 5V,12V line at the installation ambient; consider two supplies Hold: read the Others line at the installation ambient; consider two supplies

LED Strip Power Supply Quote Checklist

A useful request describes the installation, not only a target wattage. Copy the template below into the quote form and include the strip and controller part numbers with links to their datasheets.

When several supplies will share one circuit, note that the LPV-100 specification lists a typical cold-start inrush current of 75A at 230VAC and a maximum of 2 units on a 16A type B circuit breaker, or 3 units on type C, at 230VAC. The circuit design itself belongs to a qualified installer.

  • Strip: manufacturer and part number, nominal voltage, documented W/m or A/m, constant-voltage or constant-current type
  • Lengths: length of each run, how runs are grouped, and the manufacturer's maximum run length per feed
  • Input supply: site mains voltage and frequency, and how many supplies share each circuit
  • Dimming: controller or dimmer model, dimming method and channel current limits
  • Environment and destination: indoor or outdoor, enclosure, ambient temperature, and the country of installation
  • Quantity and delivery destination

Frequently asked questions

Should I choose by voltage or watts first?

Voltage first. A constant-voltage strip must run at its labelled voltage, so a 24V strip needs a 24V supply whatever the wattage. Only then compare watts or current: the connected load plus the controller's consumption must fit inside the supply's rating after derating.

Can one supply feed several strip runs?

Often, provided the total of all runs and the controller fits the supply's documented rating after derating, and each run is fed the way the strip manufacturer specifies. In the hypothetical example, three runs totalling 93.6W plus the controller come to 4.0A on LPV-100-24, close to its 4.2A rating, which is why splitting the runs across two supplies stays on the table.

Why does a sufficiently rated supply still give uneven brightness?

Because the supply rating says nothing about the voltage at the far end of a run. Voltage drop in the strip and its cables grows with current and length, and at 12V the same power draws twice the current it does at 24V. Feed arrangement, run length limits and controller channels decide how even the light is, so follow the strip manufacturer's installation instructions.

Information needed for a configuration check

  • LED strip datasheet: nominal voltage, documented W/m or A/m, and maximum run length per feed
  • Installed length of each run and how the runs are grouped
  • Controller or dimmer datasheet: input voltage, channel and total current limits, own consumption
  • Installation ambient temperature, enclosure, water and sunlight exposure
  • Site mains voltage and the number of supplies per circuit
  • Country of installation and whether the lighting is a luminaire application

Manufacturer documents used