MEAN WELL Terminal Labels and Wiring Documents
What AC/L, AC/N, FG, +V and -V mean on MEAN WELL supplies, with LRS-350 and HDR-60 pin tables, the input selector switch and where the wiring drawing is.
Use the wiring information printed for your exact model, never a diagram borrowed from a similar one. Start from the complete model number, open that model's official specification, and read its terminal pin assignment, input rows and mechanical drawing, which also points to MEAN WELL's installation manual. The two examples here show why: on LRS-350 terminal 1 is AC/L and there is an FG terminal, while on HDR-60 terminals 1 and 2 are -V and there is no FG terminal. This guide explains how to find and read those documents. It is not a wiring instruction; connection work belongs to a qualified person following the official manual with the supply isolated.
Full MEAN WELL Model Number and Document Revision
The document you need depends on the complete model number, not the series name. MEAN WELL's model encoding builds the number from the series name, the output power and the output voltage: the LRS-350 pages describe a 350W single-output series and the HDR-60 pages a 60W DIN-rail series, each followed by the output voltage. LRS-350-24 is therefore the 24V model rated at 350.4W, and HDR-60-24 the 24V model rated at 60W.
Record the exact model as printed on the label, including any suffix, and the revision of the document you use. Every specification page carries a file name and issue date in its footer; keep that with your records, because details and approvals can differ between revisions and between models of one series. On the LRS-350 pages, for instance, some approvals are marked for the 12V and 24V models only.
Where to Find the Mechanical and Wiring Drawing
In both PDFs, page 4 is the mechanical specification. It carries the case number, the dimensions and their tolerance, the terminal pin assignment table and a reference to MEAN WELL's installation manual page. That page, for the exact model and revision, is the starting point for any connection work.
The installation manual itself is a separate document and is not reproduced here. Obtain it for the exact model from the manufacturer's page named on the drawing, and treat the drawing and the manual together as the reference; if they disagree with each other or with the unit in front of you, stop and ask.
Reading the Terminal Pin Assignment Table
Read the pin assignment table exactly as printed. The two examples use the same kind of labels but put them in different places, so a terminal number on its own means nothing without the model.
AC/L and AC/N are the mains line and neutral inputs, FG is the frame-ground terminal, and -V and +V are the DC output. Where a label is absent from the table, as FG is on HDR-60, do not assume a hidden equivalent; HDR-60 lists isolation class II among its features. Where the table groups several pins, such as 4~6 on LRS-350, it defines terminals of one function; it does not tell you how many conductors to connect, which is a question for the manual.
| Terminal | LRS-350 | HDR-60 |
|---|---|---|
| 1 | AC/L | -V |
| 2 | AC/N | -V |
| 3 | FG | +V |
| 4 | DC OUTPUT -V (group 4~6) | +V |
| 5 | DC OUTPUT -V (group 4~6) | AC/L |
| 6 | DC OUTPUT -V (group 4~6) | AC/N |
| 7 to 9 | DC OUTPUT +V | No terminal |
Input Voltage Selection: LRS-350 and HDR-60
Input information sits in the specification table, not on the drawing. LRS-350 lists 90 ~ 132VAC / 180 ~ 264VAC selected by switch, and 240 ~ 370VDC only with the switch on 230VAC; its features describe the AC input range as selectable by switch. The switch position therefore has to match the site supply before the unit is energised, and the input rows that apply change with it.
HDR-60 lists a universal input of 85 ~ 264VAC (277VAC operational) and 120 ~ 370VDC (390VDC operational), with no selector. Both pages also list inrush current, 60A/115VAC and 60A/230VAC for LRS-350 and 30A/115VAC and 60A/230VAC for HDR-60, and an over voltage category III rating with altitude up to 2000 meters; the installer needs these when choosing upstream protection.
Mounting and Environmental Limits on the Drawing
The drawing and environment rows set installation limits that the pin table does not. LRS-350 is an enclosed unit of 215*115*30mm with forced air cooling by a built-in DC fan; its drawing marks the air flow direction and M4 mounting holes labelled L=3mm and L=5mm (both sides). HDR-60 is a DIN-rail unit of 52.5*90*54.5mm for TS-35/7.5 or TS-35/15 rails, cooled by free air convection.
Operating limits differ too. LRS-350 lists a working temperature of -25 ~ +70℃ with a derating curve and an operating altitude up to 5000 meters, with ambient derating of 5℃/1000m above 2000m; HDR-60 lists -30 ~ +70℃ with its own derating curve and an operating altitude of 2000 meters. Check the curve and notes of the exact model rather than the headline range.
What This Guide Does Not Replace
This guide helps you find and read the right documents before you buy or replace a supply. It does not replace the installation manual, the equipment maker's instructions or local electrical rules, and it gives no wiring procedure. The PDFs set the same boundary from the other side: both describe the power supply as a component to be installed into final equipment, which must be re-confirmed for EMC.
- Isolate the supply from the mains before any terminal work, and leave mains connections to a qualified person
- Never bypass fuses, protective earth or interlocks, and never probe exposed mains terminals
- Do not transfer a terminal map from another model, series or revision
- Keep the final equipment's own safety and EMC checks in the project plan
- Treat any mismatch between label, drawing and manual as a stop point, not a judgement call
Help Matching a Unit to Its Datasheet
If the label is unreadable, the suffix is unclear or the drawing does not match the unit, stop and ask for document matching before ordering or wiring. Send the complete model number and suffix exactly as printed on the label, the document revision you have, the site input voltage and the mounting type.
The product data policy explains where the catalog data comes from and how corrections are handled, and the product pages for LRS-350-24 and HDR-60-24 hold the model-specific data.
Frequently asked questions
Can I use a diagram for a similar model?
No. Terminal numbering and labels are model-specific: terminal 1 is AC/L on LRS-350 but -V on HDR-60, and only LRS-350 has an FG terminal. Use the drawing for the exact model and revision, together with its installation manual.
Are terminal labels and positions identical?
Not across series. Both examples use AC/L, AC/N, -V and +V labels, but in different positions and groupings, and FG appears only on LRS-350. Even within one series, confirm the drawing of the exact model and revision.
Where is the correct input-voltage information?
In the input rows of the exact model's specification table, not on the terminal drawing. LRS-350 lists 90 ~ 132VAC / 180 ~ 264VAC selected by switch, while HDR-60 lists 85 ~ 264VAC (277VAC operational). The label on the unit and the installation manual should agree with those rows.
Information needed for a configuration check
- Complete model number and suffix exactly as printed on the label
- Document revision: file name and issue date in the PDF footer
- Site mains voltage and frequency
- Mounting type, orientation and available space
- Installation ambient temperature and altitude
Manufacturer documents used
- LRS-350-SPEC.PDF, consulted pages 1, 2, 4
- HDR-60-SPEC.PDF, consulted pages 1, 2, 4