Do not choose between LRS and RSP on family names. For the exact pair compared here, LRS-350-24 is rated 24V at 14.6A (350.4W) with a 21.6~28.8V adjustment range and 88% typical efficiency, while RSP-320-24 is rated 24V at 13.4A (321.6W) with a 20 ~ 26.4V adjustment range, 89% typical efficiency and 150mVp-p maximum ripple & noise. The RSP-320 series is designated with PFC function and lists an 88 ~ 264VAC input range, whereas the LRS-350 input is 90 ~ 132VAC / 180 ~ 264VAC selected by switch. Neither model is a confirmed drop-in replacement for the other; have load current, derating, mechanics and approvals checked by a qualified person before buying.
Set the comparison scope
LRS and RSP are MEAN WELL family names, not single products. Each family spans several output voltages and power levels, so a name alone cannot tell you which supply fits a given machine or panel. This guide compares only the exact models LRS-350-24 and RSP-320-24, and no figure quoted here is extended to other family members.
The LRS side is read from the LRS-350 specification and the RSP side from the RSP-320 specification, both listed under the manufacturer documents at the end of this page. Where a value sits in a series-wide row rather than an exact-model field, that limitation is stated, and the mechanical drawings should still be reviewed by a qualified person before installation.
Build a model-specific specification matrix
The matrix below lists only values extracted from each model's own specification page. Typical efficiency is a typical figure under the datasheet's stated measurement conditions, not a guaranteed minimum, and the RSP ripple figure is a maximum under the datasheet's stated measurement method.
| Attribute | LRS-350-24 | RSP-320-24 |
|---|---|---|
| Rated DC output voltage | 24V | 24V |
| Rated current | 14.6A | 13.4A |
| Current range | 0~14.6A | 0 ~ 13.4A |
| Rated power | 350.4W | 321.6W |
| Output voltage adjustment range | 21.6~28.8V | 20 ~ 26.4V |
| Efficiency (typical) | 88% | 89% |
| Ripple & noise (max.) | 150mVp-p | 150mVp-p |
Explain differences that change a buying decision
Three verified distinctions matter most. First, input method: the LRS-350 specification table lists an AC input of 90 ~ 132VAC / 180 ~ 264VAC by switch, so the installed position must match the switch setting; the RSP-320 table lists 88 ~ 264VAC without switch selection. Second, the RSP-320 series is designated by the manufacturer as a 320W single-output series with PFC function, which is a series-level designation to verify for the exact model, not a generic family assumption. Third, ambient capability: the LRS-350 table lists a working temperature of -25 ~ +70℃ and the RSP-320 table lists -30 ~ +70℃, each expressly subject to its derating curve.
- Marketed power-class wording is not the exact rating: the documents give 350.4W for LRS-350-24 and 321.6W for RSP-320-24.
- Rated current differs: 14.6A for LRS-350-24 versus 13.4A for RSP-320-24 at a 24V output.
- Adjustment ranges differ: 21.6~28.8V versus 20 ~ 26.4V; a load trimmed above 26.4V is outside the RSP-320-24 range shown here.
- Cooling control differs: LRS-350 documents a built-in DC fan with fan ON/OFF control; RSP-320 documents a built-in DC fan with fan-speed control.
- Typical efficiency figures of 88% and 89% are typical values under stated datasheet conditions, not like-for-like guarantees.
Check the installation and load requirements
Both mechanical drawings list the same envelope of 215*115*30mm (L*W*H), and both show terminal assignments of AC/L on pin 1, AC/N on pin 2, FG on pin 3, DC OUTPUT -V on pins 4~6 and DC OUTPUT +V on pins 7~9. Identical listed dimensions and matching terminal labels do not prove interchangeability: fixing points, clearances, airflow direction and wiring practice must be checked against each model's installation manual and reviewed by a qualified person.
- Confirm the required continuous and peak load current against the rated current of whichever exact model is being considered.
- Check ambient temperature against the working temperature row and the published derating curve for the exact model.
- Verify enclosure space for 215*115*30mm plus wiring and service clearance, not just the bare envelope.
- Confirm the site mains input and, for the LRS side, that the input-switch setting matches the installation.
- Check any approvals your end equipment requires; a component-level statement in a datasheet does not transfer automatically to finished equipment.
Work through the example pair
Do not treat a family label as an exact rated-power value. The documents state 350.4W for LRS-350-24 and 321.6W for RSP-320-24, with rated currents of 14.6A and 13.4A respectively at 24V.
Hypothetical sizing check (not a measured system): assume a continuous 24V load of 14.0A. Using headroom = rated current − hypothetical load current, LRS-350-24 (14.6A) leaves 0.6A of headroom, while RSP-320-24 (13.4A) falls 0.6A short. This is an arithmetic illustration only; real selection must apply the derating curve, ambient temperature and peak-load behaviour, reviewed by a qualified person.
Define when neither is a confirmed substitute
Nothing in the two specification documents establishes that either model is a substitute, drop-in replacement or automatic upgrade for the other. Neither specification covers equipment-side documentation such as PLC, LED module/strip, controller or dimmer manuals, so compatibility with your equipment cannot be asserted from these documents alone.
- Your equipment's own manuals (controller, LED load or PLC) define its supply requirements; this comparison cannot see them.
- Price, availability and lead time are not part of this comparison; they are confirmed in a quotation.
- Approvals described in the datasheets are component-level statements under stated conditions; end-equipment approval must be re-confirmed.
- Treat both models as candidates, not a confirmed choice, until load, thermal, mechanical and approval checks are complete.
Select a family or request comparison help
If the checks above match one exact model, review that model's own product page before ordering; if the load profile, environment or approvals are unclear, send the load schedule and site conditions with a quote request so the comparison is made on exact-model data rather than family names.
Frequently asked questions
Is RSP a direct replacement for LRS?
Not on the documented data. The two specification documents show different rated currents (13.4A for RSP-320-24 versus 14.6A for LRS-350-24), different rated power (321.6W versus 350.4W), different adjustment ranges and different input arrangements. Neither model is presented as a substitute or drop-in replacement; any substitution must be confirmed by qualified review against the actual load, derating, mechanical fit and approval requirements.
Does matching 24V prove compatibility?
No. Matching the 24V nominal output is only one parameter. The adjustment ranges differ (21.6~28.8V for LRS-350-24 versus 20 ~ 26.4V for RSP-320-24), the rated currents differ (14.6A versus 13.4A), and working temperature, ripple, protections and derating conditions must each be checked against the load. Confirm every parameter on the exact model's own specification page before ordering.
Which differences need mechanical review?
Both documents list the same 215*115*30mm (L*W*H) envelope and both drawings show AC/L on pin 1, AC/N on pin 2, FG on pin 3, DC OUTPUT -V on pins 4~6 and DC OUTPUT +V on pins 7~9. That does not prove interchangeability: fixing points, clearances, airflow direction and wiring practice must be checked against each model's installation manual, and the mechanical drawings should be reviewed by a qualified person before installation.
Information needed for a configuration check
- Continuous and peak load current required at 24V
- Ambient temperature and ventilation/airflow inside the enclosure
- Site mains input (115VAC or 230VAC class) and whether a switch-selectable input is acceptable
- Mounting orientation, fixing points and service clearance available in the enclosure
- Installation altitude of the final equipment
- Hold-up time or ride-through the load requires
- Safety, EMC or harmonic-current approvals required by the end equipment and its destination market
- Equipment-side manuals (PLC, LED module/strip, controller or dimmer) that specify supply requirements
Manufacturer documents used
- LRS-350-SPEC.PDF, consulted pages 1, 2, 3, 4
- RSP-320-SPEC.PDF, consulted pages 1, 2, 3, 4