MEAN WELL LOP-500 Series
Approvals and compliance
From the manufacturer's datasheet for this seriesUnited States
- UL
UL Listing or Recognition means UL Solutions tested samples against the applicable UL safety standard and audits the factory that builds them. A UL file number is the usual evidence an inspector or specifier asks for in North America.
Europe
- TÜV
A TÜV certificate is third-party testing against the European EN standard. It is the evidence behind a CE declaration rather than a replacement for it: CE remains the manufacturer's own declaration, and the TÜV report is what makes that declaration defensible.
International
- CB Scheme
A CB Test Certificate reports testing against the IEC standard and is accepted by member certification bodies as the basis for a national approval. It shortens a new-country approval rather than granting market access by itself, so it is the most useful item on this list when you are entering a market that is not shown here.
China
- CCC
China Compulsory Certification. Mandatory for the product categories in its scope; where it applies, a shipment without it is not clearable. Certification is against the GB standard the datasheet cites.
Eurasian Economic Union
- EAC
Conformity with the Eurasian Economic Union technical regulations, covering Russia, Belarus, Kazakhstan, Armenia and Kyrgyzstan. TP TC 004 is the low-voltage regulation and TP TC 020 the electromagnetic-compatibility one, so which number appears tells you what was assessed.
Australia and New Zealand
- RCMSupplier declaration
The Regulatory Compliance Mark covers electrical safety and electromagnetic compatibility for Australia and New Zealand. It is applied by a registered local supplier against an AS/NZS standard, which is why the datasheet cites AS/NZS numbers alongside it.
| Withstand voltage | I/P-O/P:4KVac I/P-FG:2KVac O/P-FG:1.5KVac |
|---|---|
| Isolation resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
| EMC emission | Parameter Conducted & Radiated Standard Test Level / Note |
Standards certified against
- ANSI / AAMI ES60601-1
- AS/NZS 61558-1/-2-16
- EN 60335-1
- EN 60601-1
- EN 61558-1/-2-16
- EN60335-1
- EN60601-1
- EN61558-1/-2-16
- EN62368-1
- GB4943.1
- IEC60335-1
- IEC60601-1
- IEC61558-1/-2-16
- IEC62368-1
- UL 62368-1
- UL62368-1
Read the datasheet's exact wording
CB IEC62368-1, IEC60335-1, IEC61558-1/-2-16, IEC60601-1; TUV BS EN/EN62368-1, BS EN/EN60335-1, BS EN/EN61558-1/-2-16, BS EN/EN60601-1(3.2 Version); UL UL62368-1, ANSI / AAMI ES60601-1(3.2 Version) ; CCC GB4943.1 ; RCM AS/NZS 61558-1/-2-16; EAC TPTC 004 approved. IEC/EN 61558-1/-2-16(OVC Ⅲ, altitude up to 2000M ) IEC/EN/UL 62368-1 (OVC Ⅱ, altitude up to 5000M ) IEC/EN 60335-1 (OVC Ⅱ, altitude up to 5000M ) IEC/EN 60601-1 (OVC Ⅱ, altitude up to 4000M )
Reproduced unedited from the manufacturer's datasheet. Where an approval covers only some models, the wording says so. Ask us for the certificate itself if your approval process needs it.
Request a bulk quote
Choosing between several models in this series? Send us the shortlist and we will come back with pricing, lead time and stock for each part number.
- 1 Tell us the models and quantities you are considering.
- 2 We confirm availability and send tiered pricing for the series.
- 3 Approve the quotation and we issue the invoice and shipping documents.
Request a MEAN WELL LOP-500 Series quote
Select the models you need, or describe your requirement and we will help you choose.